견적낼 때 가끔 사용하는 것.
1. 3φ TR 용량에 따른 CT. FUSE. MOF(A) 선정표
구분 |
COS & PF [A] |
MOF |
CT [A] | |||||
kVA |
MAIN |
FEEDER |
22.9kV |
6.6kV |
3.3kV |
440V |
380V | |
100 |
6 |
3 |
5 |
|
10 |
20 |
150 |
200 |
150 |
8 |
6 |
5 |
|
15 |
30 |
250 |
300 |
200 |
10 |
8 |
10 |
5 |
20 |
40 |
300 |
400 |
250 |
12 |
10 |
10 |
10 |
25 |
50 |
400 |
500 |
300 |
15 |
10 |
10 |
10 |
30 |
70 |
500 |
600 |
350 |
20 |
12 |
10 |
10 |
30 |
70 |
600 |
600 |
400 |
20 |
12 |
15 |
15 |
40 |
80 |
600 |
750 |
450 |
20 |
15 |
15 |
15 |
50 |
100 |
750 |
800 |
500 |
25 |
20 |
15 |
15 |
50 |
100 |
800 |
1000 |
550 |
25 |
20 |
15,20 |
15 |
60 |
120 |
1000 |
1000 |
600 |
30 |
25 |
20 |
20 |
60 |
120 |
1000 |
1200 |
650 |
30 |
25 |
20 |
20 |
75 |
150 |
1000 |
1200 |
700 |
40 |
25 |
20 |
20 |
75 |
150 |
1000 |
1500 |
750 |
40 |
30 |
20,30 |
25 |
75 |
150 |
1200 |
1500 |
800 |
40 |
30 |
30 |
25 |
80 |
150 |
1200 |
1500 |
850 |
50 |
30 |
30 |
25 |
100 |
200 |
1500 |
1500 |
900 |
50 |
30 |
30 |
30 |
100 |
200 |
1500 |
1500 |
1000 |
50 |
40 |
30 |
30 |
100 |
200 |
1500 |
2000 |
1100 |
50 |
40 |
30,40 |
30 |
120 |
250 |
2000 |
2000 |
1200 |
65 |
50 |
40 |
40 |
150 |
250 |
2000 |
2500 |
1400 |
65 |
50 |
40 |
40 |
150 |
300 |
|
|
1500 |
80 |
50 |
40,50 |
50 |
150 |
300 |
|
|
1600 |
80 |
65 |
50 |
50 |
150 |
300 |
|
|
1700 |
80 |
65 |
50 |
50 |
200 |
400 |
|
|
1800 |
100 |
65 |
50,75 |
75 |
200 |
400 |
|
|
1900 |
100 |
65 |
50,75 |
75 |
200 |
400 |
|
|
2000 |
100 |
80 |
75 |
75 |
200 |
400 |
|
|
2300 |
100 |
80 |
75 |
75 |
250 |
500 |
|
|
2500 |
1400 |
100 |
75 |
75 |
250 |
500 |
|
|
2600 |
1400 |
100 |
75,100 |
75 |
300 |
600 |
|
|
2900 |
1400 |
100 |
75,100 |
100 |
300 |
600 |
|
|
3000 |
1400 |
100 |
100 |
100 |
300 |
600 |
|
|
2. 0.6/1kV CV 허용전류 및 허용용량
No. |
규격(㎟) |
허용전류 |
용량(kVA) | ||
KS |
IEC |
A |
220V |
380V | |
1 |
2 |
|
32 |
7 |
21 |
2 |
3.5 |
2.5 |
45 |
9 |
29 |
3 |
5.5 |
4 |
60 |
13 |
39 |
4 |
8 |
6 |
74 |
16 |
48 |
5 |
14 |
10 |
103 |
22 |
67 |
6 |
22 |
16 |
136 |
29 |
89 |
7 |
38 |
25/35 |
192 |
42 |
126 |
8 |
60 |
50/70 |
257 |
56 |
169 |
9 |
100 |
95/120 |
355 |
78 |
233 |
10 |
150 |
150 |
458 |
100 |
301 |
11 |
200 |
185 |
547 |
120 |
360 |
12 |
250 |
240 |
625 |
137 |
411 |
13 |
325 |
300 |
733 |
161 |
482 |
14 |
400 |
400 |
829 |
182 |
545 |
15 |
500 |
500 |
939 |
206 |
618 |
16 |
600 |
630 |
1036 |
227 |
681 |
17 |
800 |
|
1303 |
286 |
857 |
3. 차단기 용량별 전력량
No. |
FRAME |
Ampere |
전력량(kVA) | |
220V |
380V | |||
1 |
30 |
15 |
3 |
9 |
2 |
30 |
20 |
4 |
13 |
3 |
30 |
30 |
6 |
19 |
4 |
50 |
50 |
11 |
32 |
5 |
100 |
75 |
16 |
49 |
6 |
100 |
100 |
22 |
65 |
7 |
150 |
125 |
27 |
82 |
8 |
150 |
150 |
33 |
98 |
9 |
225 |
175 |
38 |
115 |
10 |
225 |
225 |
49 |
148 |
11 |
250 |
250 |
55 |
164 |
12 |
400 |
300 |
66 |
197 |
13 |
400 |
400 |
88 |
263 |
14 |
600 |
600 |
132 |
394 |
15 |
800 |
800 |
176 |
526 |
16 |
1000 |
1000 |
220 |
658 |
'공사 > 전기' 카테고리의 다른 글
전기(정보통신)공사_준공실적증명서양식(철도신호-철도전차선) (0) | 2010.04.19 |
---|---|
전기설비규모(용량)별 전기안전관리자의 자격기준 (0) | 2009.07.22 |
실적증명서발주처미확인따른사유서 양식(한국전기공사협회) (0) | 2009.02.17 |
한전 적격심사포기각서 양식 - 단가공사 (0) | 2008.11.29 |
환입보관의뢰서(한전양식) (0) | 2008.07.24 |